3 technical data – VEGA VEGASEL 543, 544, 545, 546, 547 User Manual

Page 5

Advertising
background image

VEGASEL

5

Product description

VEGASEL 547

(corresponds to two VEGASEL 543)

Two-point level switch (hysteresis variable 1 … 99 %)

Inputs:

current 0/4 … 20 mA or
voltage 0/2 … 10 V

Outputs:

2 relays (spdt)
2 transistors

Approvals *:

as part of an overfill protection acc. to WHG and VbF

Application:

min.-/max.-control, overfill protection

*

in preparation

Level

off

off

on

on

time t

Max. 1

Max. 2

Min. 1

Min. 2

Fig. 1.6 Two-point level switch each with
variable hysteresis

1.3 Technical data

Power supply

Operating voltage

U

nenn

= 24 V AC (20 … 53 V), 50/60 Hz
= 24 V DC (20 … 72 V)

Power consumption

approx. 3 VA or approx. 2 W

Fuse

Pigtail fuse 630 mA slow below

Inputs

Voltage

0 … 10 V DC, Ri

100 k

Current

0/4 … 20 mA, Ri = 37,5

Switching threshold

adjustable via coded key

Temperature error

0,1 %/10 k relating to range

Connection line

2-wire (standard line)

Level relays

Number of relays
- VEGASEL 543

1

- VEGASEL 544

2

- VEGASEL 545

3

- VEGASEL 546

4

- VEGASEL 547

2

Contact

1 floating spdt

Contact material

AgNiO and hard gold plated

Turn-on voltage

min. 10 mV DC
max. 250 V AC, 60 V DC

Switching current

min. 10

µ

A DC

max. 2 A AC, 1 A DC

Breaking capacity

max. 125 VA, 54 W

Advertising