Diagnosis

5 Diagnosis

5.1 Maintenance

The instrument is maintenance-free.

5.2 Repair

For safety and guarantee reasons repairs on the instrument must only be carried out by VEGA-staff.

If a defect please return the instrument along with a short description of the fault to our repair department.

Interferences are short misfunctions of the instrument caused by wrong operation or defects on the sensors or
the connection lines.

Possible errors, reasons and actions are stated in "5.3 Fault finding" see below.

5.3 Fault finding

Fault

Removal / Measure

Instrument is wihout function /
green mains control lamp

extinguished

Check the power supply and mains connections acc. to the wiring information on page 9. Call

the service department if the instrument is still without function.

Instrument does not switch

correctly

Check position of the coded keys. If with a two-point level switch the min. value is above the
max. value, the two-point level switch becomes a single point level switch via a hysteresis of

0,5 %. The switch point corresponds to the max. value. Correct the adjusted values.

Instrument done correctly

Check the voltage or current input:
- Voltage/current values within the nominal ranges (see 1.3 Technical data)?

- Short circuit or line break?

- Connection not correct or wrongly polarity?
If such a fault cannot be confirmed, check the connected measuring system consisting of

sensor and signal conditioning instrument. Observe the diagnostic information in the
respective operating instructions.