2 set-up checklist, Set-up – VEGA VEGASEL 543, 544, 545, 546, 547 User Manual
Page 13
VEGASEL
13
Set-up
4.2 Set-up Checklist
The following list briefly states the essential set-up
steps:
• Measuring system consisting of VEGA-sensor to
set-up or adjust with VEGA-signal conditioning
instrument or instrument of other manufacturers
[ ] done
• Wire multiway connector in carrier or terminal strip
in the housing for VEGASEL select mode
[ ] done
• Select code
A = overfill protection
B = protection against dry running of pumps
with DIL-switches1 … 4
Mode
1. adjustment
2. adjustment
Level switch
A
B
A
B
1
2
3
4
• Select hysteresis 1 % or 3 % with DIL-switch 1 … 4
for single point level switches
Hysteresis
1. adjustment
2. adjustment
Level switch
1 %
3 %
1 %
3 %
1
2
3
4
• Select input with DIL-switch 5
[ ] voltage input (U)
[ ] current input (I)
• Plug VEGASEL into carrier or housing
[ ] done
• Adjust with coded keys in the front panel of
VEGASEL the requested switch points
Switch points
1. adjustment
2. adjustment
Level switch
in %
in %
Single point
1
2
3
4
Two-point
min.
max.
min.
max.
Note:
Set the VEGAMET signal conditioning instrument to
simulation or connect a VEGAMET as simulator for an
instrument of other manufacturers.