Set-up

4.2 Set-up Checklist

The following list briefly states the essential set-up
steps:

• Measuring system consisting of VEGA-sensor to

set-up or adjust with VEGA-signal conditioning
instrument or instrument of other manufacturers
[ ] done

• Wire multiway connector in carrier or terminal strip

in the housing for VEGASEL select mode
[ ] done

• Select code

A = overfill protection

B = protection against dry running of pumps
with DIL-switches1 … 4

Mode

1. adjustment

2. adjustment

Level switch

A

B

A

B

1
2
3

4

• Select hysteresis 1 % or 3 % with DIL-switch 1 … 4

for single point level switches

Hysteresis

1. adjustment

2. adjustment

Level switch

1 %

3 %

1 %

3 %

1
2
3

4

• Select input with DIL-switch 5

[ ] voltage input (U)

[ ] current input (I)

• Plug VEGASEL into carrier or housing

[ ] done

• Adjust with coded keys in the front panel of

VEGASEL the requested switch points

Switch points

1. adjustment

2. adjustment

Level switch

in %

in %

Single point

1
2
3
4

Two-point

min.
max.
min.
max.

Note:

Set the VEGAMET signal conditioning instrument to
simulation or connect a VEGAMET as simulator for an
instrument of other manufacturers.