VEGASEL

Set-up

4.3 Switch point adjustment

Single point level switch (VEGASEL 544, 545, 546)

Coded key 2

Coded key 1

on 1

off 1

on 1

off 1

on 2

off 2

on 2

off 2

Level

The above figure is also valid for VEGASEL with only 1, 3 or 4 relays.

The feature of a single point level switch is the switching to on/off at a point of the input signal. This switch point is
adjusted via a coded key on the front panel. The hysteresis can be selected via DIL-switches on the board
between low hysteresis (approx. 1 %) and high hysteresis (approx. 3 %). With a VEGASEL as single point level
switch the following functions can be obtained: overfill protection, protection against dry running of pumps or
switch on/off of a heating or a stirrer at certain level.

With the coded keys, the %-values are adjusted which relate to the

of the input signal.

Example:

Input4 … 20 mA, switch point at 75 % and at 25 %

= 20 mA – 4 mA = 16 mA

75 % of 16 mA = 12 mA
25 % of 16 mA = 4 mA

Switch point 75 % corresponds to 4 mA + 12 mA = 16 mA
Switch point 25 % corresponds to 4 mA + 4 mA = 8 mA

The effect of the hysteresis depends on the adjusted mode.

Example 1: Switch point 75 %, mode A, hysteresis 1 %

Switching condition: off 75 %, on 74 %

Example 2: Switch point 25 %, mode B, hysteresis 3 %

Switching condition: off 25 %, on 28 %

Time

5

7

5

2

d6 b6 z6

100%

75%

25%

0%

d10 b10 z10

d6 b6 z6

d6 b6 z6

d6 b6 z6

d6 b6 z6

d10 b10 z10

d10 b10 z10

Mode A

Relay 1

LED 1

Mode B
Relay 2

LED 2