VEGAFLEX 51V and 52V

Material cone

Note when installing VEGAFLEX into the ves-
sel that material cones can be caused with
solids which can change the measured
value. We recommend to choose an installa-
tion place where the cable detects an aver-
age value of the material cone.

Dependent on the position of the filling and
emptying opening in the vessels, VEGAFLEX
should be installed appropriately. For com-
pensation of measuring errors caused by the
material cone, you should install the cable at
a distance of

d

/

6

from the vessel wall or vessel

installation. In any case keep a min. distance
of 300 mm.

3

1

2

1 Emptying
2 Filling opening
3 VEGAFLEX

Mounting / Installation instructions