Material cone
Note when installing VEGAFLEX into the ves-
sel that material cones can be caused with
solids which can change the measured
value. We recommend to choose an installa-
tion place where the cable detects an aver-
age value of the material cone.
Dependent on the position of the filling and
emptying opening in the vessels, VEGAFLEX
should be installed appropriately. For com-
pensation of measuring errors caused by the
material cone, you should install the cable at
a distance of
d
/
6
from the vessel wall or vessel
installation. In any case keep a min. distance
of 300 mm.
3
1
2
1 Emptying
2 Filling opening
3 VEGAFLEX
Mounting / Installation instructions