5 diagnosis, 1 simulation, 2 error removal – VEGA VEGAFLEX 52V User Manual

Page 32

Advertising
background image

32

VEGAFLEX 51V and 52V

5 Diagnosis

5.1 Simulation

For simulation of a certain filling, you can
enquire the function "Simulation" on the ad-
justment module MINICOM, in the software
program VVO or in the signal conditioning
instrument VEGAMET (V).
You simulate a certain measured value. Note
that connected instruments such as e.g. a
DCS react according to their adjustments
and probably activate alarm signals or sys-
tem functions.

5.2 Error removal

Error

Error removal

E 013

Sensor does not find

- Message is displayed during feeding

level echo

phase.

- When the message remains, the DK-value

of the medium can be too low.

Check the useful and noise level.
See 4.2 Adjustment with adjustment module
MINICOM / 6. Useful and noise level.
When the message still remains, carry out
a new adjustment.

E 017

Adjustment span too small

Carry out a new adjustment.
Note that the difference between min. and
max.-adjustment is at least 10 mm.

E 036

Software-Update incorrect

Return the instrument for repair.

E 040

Hardware failure /

Check all connection lines.

electronics defect

Contact our service department.

Diagnosis

Advertising