5 Connecting to voltage supply

5.1 Preparing the connection

Generally not the following safety instructions:

l

Connect only in the complete absence of line voltage

l

If overvoltage surges are expected, overvoltage arresters

should be installed according to Profibus specification.

In hazardous areas you should take note of the appropriate

regulations, conformity and type approval certificates of the

sensors and power supply units.

If reliable separation is required, power supply and current

output are transmitted via separate two-wire connection

cables. The supply voltage range can differ depending on the

instrument version. The exact range is stated in the "Technical

data" in the "Supplement".
This instrument is designed in protection class I. To maintain

this protection class, it is absolutely necessary that the ground

conductor be connected to the internal ground terminal. Take

note of the general installation regulations.
As a rule, connect VEGASON 66 to vessel ground (potential

euqalisation) or in case of plastic vessels to the next ground

potential. For this purpose, there is a ground terminal on the

side of the instrument housing.
For power supply, an approved installation cable with PE

conductor is necessary.
VEGASON 66 is connected with screened cable acc. to

Profibus specification.
An outer cable diameter of 5 … 9 mm ensures the seal effect

of the respective cable entry.
Please make sure that your installation is carried out according

to the Profibus specification. In particular, make sure that the

termination of the bus is done with appropriate terminating

resistors.
In systems with potential equalisation, connect the cable

screen directly to ground potential at the power supply unit, in

the connection box and at the sensor. The screen in the sensor

Note safety instructions

Take note of safety

instructions for Ex

applications

Select power supply

Selecting the connection ca-

ble

Cable screening and ground-

ing

24

VEGASON 66 - Profibus PA

Connecting to voltage supply

28789

-EN