10.2 Profibus PA

Instrument master file
The instrument master file (GSD) contains the characteristic data of the Profibus PA

instrument. These data are, e.g. the permissible transmission rates as well as information on

diagnostics values and the format of the measured value outputted by the PA instrument.
A bitmap file is also provided for the planning tool of the Profibus network. This file is

automatically installed with the GSD file. The bitmap file is used for symbolic indication of the

PA instrument in the configuration tool.

Ident number

Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus

user organisation (PNO). This ID number is also included in the name of the GSD file. For

VEGASON 66 the ID number is 0x0770(hex) and the GSD file "SN__0770.GSD". As an

option to this manufacturer-specific GSD file, PNO provides also a general so-called profile-

specific GSD file. For VEGASON 66 you have to use the general GSD file "PA139701.GSD". If

the general GSD file is used, the sensor must be set to the profile-specific ident number via the

DTM software. By default, the sensor operates with the manufacturer-specific ID number.

Note:

When using the profile-specific GSD file, the PA-OUT value as

well as the temperature value are transmitted to the PLC (see

block diagram "Cyclical data traffic").

Cyclical data traffic

The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during

operation. The below block diagram below shows which data can be accessed by the PLC.

Supplement

52

VEGASON 66 - Profibus PA

28789

-EN