6.4 Setup procedure

After VEGASON 66 is connected to voltage supply or after

voltage recurrence, the instrument carries out a self-check for

approx. 30 seconds. The following steps are carried out:

l

Internal check of the electronics

l

Indication of the instrument type, the firmware as well as

the sensor TAGs (sensor designation)

l

Status byte goes briefly to fault value

Then the current measured value will be displayed and the

corresponding digital output signal will be outputted to the

cable.

3)

Before starting the actual parameter adjustment of a Profibus

PA sensor, the address setting must first be carried out. You

will find a detailed description in the operating instructions

manual of the indicating and adjustment module or in the

online help of PACTware™ or DTM.
As VEGASON 66 is a distance measuring instrument, the

distance from the sensor to the product surface is measured.

To have the real product level displayed, an allocation of the

measured distance to the percentage height must be made. To

carry out this adjustment, the distance is entered with full and

empty vessel. If these values are not known, an adjustment

with the distance values, e.g. 10 % and 90 % is also possible.

Starting point for these distance specifications is always the

the lower side of the flange (flange version, for all other

versions the lower side of the transducer.
The actual level is then calculated on the basis of these

entered values. At the same time, the operating range of the

sensor is limited from maximum range to the requested range.
The real product level during this adjustment is not important,

because the min./max. adjustment is always carried out

without changing the product level. These settings can be

made ahead of time without the instrument having to be

installed.
In the main menu item "Basic adjustment", the individual

submenu items should be selected one after the other and

provided with the correct parameter values.
Start your parameter adjustment with the following menu items

of the basic adjustment:

3)

The values correspond to the actual measured level as well as to the set-

tings already carried out, e.g. default setting.

Switch-on phase

Address setting

Parameter adjustment

Setup with the indicating and adjustment module PLICSCOM

32

VEGASON 66 - Profibus PA

28789

-EN

-060731