VEGA VEGASON 66 Profibus PA User Manual
Page 42
?
In Simatic S7 the measured value is always presented as 0
l
Only four bytes are consistently loaded in the PLC
à
Use function component SFC14 to load 5 bytes
consistently
?
Measured value on the indicating and adjustment module
does not correspond to the value in the PLC
l
The menu item "Display - Display value" is not set to
"PA-Out"
à
Check values and correct, if necessary
?
No connection between PLC and PA network
l
Incorrect adjustment of the bus parameter and the
segment coupler-dependent baud rate
à
Check data and correct, if necessary
?
Instrument does not appear during connection setup
l
Profibus DP cable pole-reversed
à
Check cable and correct, if necessary
l
Incorrect termination
à
Check termination at the beginning and end points of
the bus and terminate, if necessary, according to the
specification
l
Instrument not connected to the segment, double
assignment of an address
à
Check and correct, if necessary
In Ex applications, the regulations for the wiring of intrinsically
safe circuits must be observed.
?
E013
l
no measured value available
à
sensor in boot phase
à
sensor does not find an echo, e.g. because of faulty
installation or incorrect parameter adjustment
Fault messages via the indi-
cating/adjustment module
Maintenance and fault rectification