(numbering from top to bottom)

1 K

Ω

10 K

Ω

200 K

Ω

s

CH1

CH2

Alarm

Slave/Master

min.

min.

max.

max.

off on

1

2

3

4

5

6

7

8

Fig. 13: DIL switch block (A)

1

Sensitivity adjustment - range up to 1 kΩ

2

Sensitivity adjustment - range up to 10 kΩ

3

Sensitivity adjustment - range up to 200 kΩ

4

Two-point control

5

Mode - channel 1 (CH 1)

6

Mode - channel 2 (CH 2)

7

Line monitoring (alarm)

8

Master/Slave adjustment

l

A

1 - Sensitivity adjustment - range up to 1 kΩ

l

A

2 - Sensitivity adjustment - range up to 10 kΩ

l

A

3 - Sensitivity adjustment - range up to 200 kΩ

l

A

4 - Two-point control

l

A

5 - Mode - Channel 1 (CH 1)

-

off: Max. detection or overflow protection

-

on: Min. detection or dry run detection

l

A

6 - Mode - Channel 2 (CH 2)

-

off: Max. detection or overflow protection

-

on: Min. detection or dry run detection

l

A

7 - Line monitoring (alarm)

l

A

8 - Master/Slave adjustment (on = Master)

A potentiometer for switching point adaptation is located below the
cover of the signal conditioning instrument. With this potentiometer you
can adapt the measuring system to the conductivity of the product.

Calibration

3

1

Fig. 14: Potentiometer for switching point adjustment (B)

Potentiometer for swit-
ching point adjustment
(B)

20

VEGATOR

632 • Signal conditioning instrument

6 Adjustment elements