2 sensitivity adjustment – VEGA VEGATOR 632 User Manual

Page 25

Advertising
background image

7

.2 Sensitivity adjustment

Standard adjustment for conductive liquids.

Specifications:

The probe is covered with medium by at least 1 cm.

1

Set DIL switch 1 to 3 on the DIL switch block (A) according to the
following illustration

1 K

Ω

10 K

Ω

200 K

Ω

200 K

Ω

CH1

CH2

max.

max.

off on

1

2

3

4

5

6

7

Fig. 53: Medium: Conductive liquids up to 200 kΩ

2

Turn potentiometer (B) to complete left position

3

Turn potentiometer (B) slowly clockwise until the relay output
switches and the yellow control lamp changes condition

4

Turn the potentiometer approximately 15° in the same direction

5

If the relay output does not change, you have to switch to the next
range (10 kΩ).

If the relay output has switched, empty the vessel until the electrode is
uncovered.

The relay output must now switch again.

Adjustment in liquids with resistance range up to 10 kΩ

Specifications:

The probe is covered with medium.

Medium: Non-conducti-
ve liquids

Medium: Liquids in the
resistance range up to
10

VEGATOR

632 • Signal conditioning instrument

25

7 Set up - Single channel control (level detection)