9 set up – two–channel control, 1 adjust relay function, 9set up - two-channel control – VEGA VEGATOR 632 User Manual

Page 35

Advertising
background image

9

Set up - Two-channel control

9

.1 Adjust relay function

3-step switch. The individual switch positions are assigned as follows:

1

2

3

4

5

6

7

8

O

N

3

1

3362

CH1 output parallel

CH2 output separate

CH1 with alarm

Fig. 100: Slide switch for adjustment of the relay outputs (D)

l

CH

1 output parallel - Both relay outputs switch in parallel

l

CH

2 output separate - Relay outputs switch separately

l

CH

1 with alarm - Fault signal with relay output 2

The following charts provide an overview of the relay switching
conditions and the control lamps depending on the adjusted mode and
level.

Output relay 2 operates like output relay 1. The function of the two
output relays is the same.

Switching reaction of the two channels see "CH 2 output separate".

Not useful for two-channel control.

Two-channel control - max./min.
Specifications:

l

Channel 1: Overfill protection (max.) DIL switch block (A) switch 5
to off

l

Channel 2: Dry run protection (min.) DIL switch block (A) switch 6
to on

l

Channel 1 (relay 1) and channel 2 (relay 2) switch separately (CH
2 output separate)

l

Two-channel control (two separate switching points) - DIL switch
block (A) switch 4 to off

Adjustment of the relay
outputs (slide switch D)

CH 1 output parallel

CH 2 output separate

VEGATOR

632 • Signal conditioning instrument

35

9 Set up - Two-channel control

35243

-EN

-120228