3 function test, 12 .3 function test – VEGA VEGATOR 632 User Manual

Page 51

Advertising
background image

l

Signal conditioning instrument defective

à Exchange VEGATOR 632

l

Probe mechanically damaged

à Exchange probe

l

Conductivity of the product too low

à Check if the conductivity value of your product is at least

7.5 µS/cm

l

Welded contacts - for example after a shortcircuit

à Exchange VEGATOR 632. If necessary, integrate a fuse into

the contact circuit

?

Wrong switching function of the signal conditioning instrument.

l

Wrong setting of the change over switch for the level signal

à Set the change over switch for the level signal correctly. See

chapter "Adjustment".

12

.3 Function test

For simulation of a fault signal you can remove the upper plug
connection from VEGATOR 632.

b

a

Fig. 139: Function test

The instruments signals a failure and the switching relays take on
deenergized (safe) condition.

Simulation of a fault sig-
nal

VEGATOR

632 • Signal conditioning instrument

51

12 Maintenance and fault rectification

35243

-EN

-120228