VEGA VEGATOR 632 User Manual
Page 32
Adjustment in liquids with resistance range up to 10 kΩ.
Specifications:
The probe is covered with medium.
1
Set DIL switch 1 to 3 on the DIL switch block (A) according to the
following illustration
1 K
Ω
10 K
Ω
200 K
Ω
10 K
Ω
CH1
CH2
max.
max.
off on
1
2
3
4
5
6
7
Fig. 96: Resistance range up to 10 kΩ
2
Turn potentiometer (B) to complete left position
3
Turn potentiometer (B) slowly clockwise until the relay output
switches and the yellow control lamp changes condition
4
Turn the potentiometer approximately 15° in the same direction
5
If the relay output does not change, you have to switch to the next
range.
If the relay output has switched, empty the vessel until the electrode is
uncovered.
The relay output must now switch again.
Adjustment in liquids with resistance range up to 1 kΩ.
Specifications:
The probe is covered with medium.
Resistance range up to
10
kΩ
Resistance range up to
1
kΩ
32
VEGATOR
632 • Signal conditioning instrument
8 Set up - Two-point control Δs (pump control)
35243
-EN
-120228