6 Set up with the display and adjustment module

SOLITRAC 31 • 4 … 20 mA/HART - four-wire

40090-EN-131119

The address setting (MGC) on the Slave instruments can be freely

selected. Only the address "0 - 0" is reserved for the Master instru-

ment.
The Master instrument must have the function "Level". For this

purpose, select under the menu item "Setup/Application" the function

"Level".

Set the address setting (MGC) on the Master instrument to "0 - 0".
You have to enter the addresses of the Slave instruments in the list of

the Master instrument. This function is not possible in the supply and

adjustment module. To do this you need PACTware with the respective

DTM.

The main menu is divided into five sections with the following func-

tions:

Setup: Settings, e.g. for measurement loop name, isotope, applica-

tion, background radiation, adjustment, signal output
Display: Settings, for example language, measured value display
Diagnosis: Information, for example, of device status, peak value,

simulation
Additional adjustments: Instrument unit, reset, date/time, copying

function
Info: Instrument name, hardware and software version, date of manu-

facture, instrument features

Check if the correct language is already set for the display. If not, you

can change the language in the menu item "Display/Language".

Start with the setup of SOLITRAC 31.
In the main menu point "Setup", the individual submenu points

should be selected one after the other and provided with the correct

parameters to ensure optimum adjustment of the measurement. The

procedure is described in the following.
Stick with the normal sequence of the menu items as closely as pos-

sible.

Main menu

Procedure