6 Set up with the display and adjustment module

SOLITRAC 31 • 4 … 20 mA/HART - four-wire

40090-EN-131119

The peak value function holds the max. and min. values during opera-

tion.
This parameter is described in the operating instructions manual

"Display and adjustment module".

Here, you can retrieve the adjustment value of the sensor. This is the

percentage value of the max. pulse rate at which the sensor switches

over.
If you have carried out a single point adjustment, this is the entered

value. With a two-point adjustment, this is the calculated value.
The value is an indication for the reliability and reproducibility of the

switching point.
The greater the difference in the pulse rate between covered and

uncovered status, the greater the differential value (Delta I) and the

more reliable the measurement. The automatically calculated damp-

ing is also oriented around the Delta I value. The higher the value, the

lower the damping.
A Delta I value below 10 % is an indication for a critical measurement.

In this menu item you can simulate measured values via the current

output. This allows the signal path to be tested, e.g. through down-

stream indicating instruments or the input card of the control system.
You can simulate different values:

Pulse rate of the sensor

Current output

Switching function of the relay

Diagnosis - Peak value

Diagnosis - Adjustment

data

Diagnosis/Simulation