9 Diagnostics and service

SOLITRAC 31 • 4 … 20 mA/HART - four-wire

40090-EN-131119

Code
Text mes-

sage

Cause

Rectification

F120
Filter time

error

– Faulty or missing instrument

adjustment

– Carrying out adjustment

F121
Faulty partici-

pant list on the

multisensor

communica-

tion bus

– Slave instruments not found

– Check Slave instruments

– Check Slave list in Master

instrument

– Slave instrument with wrong

address

F122
Double ad-

dresses on

the mul-

tisensor

communica-

tion bus

– Instrument addresse was

assigned several times

– Change instrument

addresses

F123
X-ray alarm

– External instruments cause

radiation

– Determine reason for X-ray

alarm

– In case of brief X-ray radia-

tion: Monitor switching out-

puts for this time manually

F124
Alarm due to

increased ra-

diation

– Radiation dose too high

– Determine reason for

increased radiation

F125
Ambient tem-

perature too

high

– Ambient temperature on

the housing outside the

specification

– Cool the instrument or pro-

tect it with isolating material

against radiation heat

The following table shows the error codes and text messages in the

status message "Function check" and provides information on causes

as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

C029
Simulation

– Simulation active

– Finish simulation

– Wait for the automatic end

after 60 mins.

The following table shows the error codes and text messages in the

status message "Out of specification" and provides information on

causes as well as corrective measures.

Function check

Out of specification