11 Supplement

SOLITRAC 31 • 4 … 20 mA/HART - four-wire

40090-EN-131119

Ʋ Max.

3 A AC, 1 A DC

Breaking capacity

Ʋ Min.

50 mW

Ʋ Max.

750 VA AC, 40 W DC
If inductive loads or stronger currents are switched

through, the gold plating on the relay contact surface will

be permanently damaged. The contact is then no longer

suitable for switching low-level signal circuits.

Contact material (relay contacts)

AgNi or AgSnO and Au plated

Transistor output
Output

Floating transistor output, permanently shortcircuit-proof

Load current

< 400 mA

Voltage loss

< 1 V

Switching voltage

< 55 V DC

Blocking current

< 10 µA

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Repeatability

≤ 0.5 %

Deviation with bulk solids

The values depend to a great extent on the application.

Binding specifications are thus not possible.

Deviation under EMC influence

≤ 1 %

Variables influencing measurement accuracy
Specifications apply also to the current output
Temperature drift - Current output

±0.03 %/10 K relating to the 16 mA span max. ±0.3 %

Deviation on the current output through

analogue/digital conversion

<±15 µA

Deviation on the current output due to

strong, high frequency electromagnetic

interference acc. to EN 61326

<±150 µA

Characteristics and performance data
Step response time

5)

≤ 5 s (with damping 1 s)

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +60 °C (-40 … +140 °F)

5)

Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk

solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).