2 connection procedure – VEGA VEGAWELL 72 4 … 20 mA_HART PT 100 User Manual

Page 19

Advertising
background image

connected directly to the internal ground terminal. The ground
terminal outside on the housing must be connected to the
potential equalisation.

I

f potential equalisation currents are expected, the connection

on the processing side must be made via a ceramic capacitor
(

e. g. 1 nF, 1500 V). The low frequency potential equalisation

currents are thus suppressed, but the protective effect against
high frequency interference signals remains.

T

ake note of the corresponding installation regulations for Ex

applications.

5

.2 Connection procedure

P

roceed as follows:

1

W

ire the connection cable up to the connection compart-

ment. The bending radius must be at least 25 mm.

3)

2

C

onnect the wire ends to the screw terminals according to

the wiring plan

P

roceed as follows:

1

S

nap VEGABOX 02 onto the carrier rail or screw it to the

mounting plate

2

L

oosen the cover screws and remove the cover

3

S

hift the cable throught the cable entry into VEGABOX 02

4

L

oosen the screws with a screwdriver

5

I

nsert the wire ends into the open terminals according to

the wiring plan

6

T

ighten the screws with a screwdriver

7

C

heck the hold of the wires in the terminals by lightly

pulling on them

8

T

ighten the compression nut of the cable entry. The seal

ring must completely encircle the cable

9

C

onnect the supply cable according to steps 3 to 8

10 S

crew the housing cover on

T

he electrical connection is finished.

P

roceed as follows:

1

U

nscrew the housing cover

3)

T

he connection cable is already preconfectioned. After shortening the ca-

ble, fasten the type plate with support again to the cable.

Select connec-
tion cable for Ex
applications

Direct connection

Connection via
VEGABOX 02

Via the housing

VEGAWELL

72 • 4 … 20

mA/HART PT

19

5 C

onnecting to power supply

34360

-

EN

-080806