4 Mounting

VEGAPULS 68 • Profibus PA

36537-EN-130205

4 Mounting

4.1 General instructions

With instruments with threaded process fitting, suitable tools must be

applied for tightening the hexagon.

Warning:

The housing must not be used to screw the instrument in! Applying

tightening force can damage internal parts of the housing.

Use the recommended cables (see chapter "Connecting to power

supply") and tighten the cable gland.
You can give your instrument additional protection against moisture

penetration by leading the connection cable downward in front of

the cable entry. Rain and condensation water can thus drain off. This

applies mainly to outdoor mounting as well as installation in areas

where high humidity is expected (e.g. through cleaning processes) or

on cooled or heated vessels.

Make sure that all parts of the instrument exposed to the process, in

particular the active measuring component, process seal and process

fitting, are suitable for the existing process conditions. These include

above all the process pressure, process temperature as well as the

chemical properties of the medium.
You can find the specifications in chapter "Technical data" and on the

type label.

4.2 Mounting preparations - Horn antenna

The instrument is also available in versions with an antenna whose

diameter is larger than the process fitting (thread, flange). In such ca-

ses the antenna must be disconnected from the process fitting before

mounting. Proceed as follows:
1. Loosen the hexagon socket screws (3) on the antenna socket

with an Allen wrench (size 3)

2. Remove the antenna (4)
Note:

The plastic cone may not be pulled out of the antenna socket.
3. Insert the antenna from below into the vessel socket and secure it

against falling off

4. Retighten the antenna with hexagon screws to the antenna so-

cket; torque max. 2.5 Nm (1.8 lbf ft)

Note:

The radar sensor with rinsing air connection or antenna extension

is provided with a notch on the antenna socket. This notch must be

aligned with the marking on the process fitting (the marking specifies

the position of the polarisation plane of the radar signal).