Measurement error during emptying – VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual

Page 60

Advertising
background image

60

9 Diagnosis, Asset Management and service

VEGAPULS 68 • Profibus PA

36537-EN-130205

Measurement error during filling

Fault description

Error pattern

Cause

Rectification

3rd measured value

jumps towards 0 % du-

ring filling

Level

time

0

– Amplitude of a multiple echo

(vessel top - product surface) is

larger than the level echo

– Check parameter "Application",

especially vessel top, product

type, dished end, high dielectric

figure, adapt if necessary

– The level echo cannot be distin-

guished from the false echo at

a false echo position (jumps to

multiple echo)

– Remove/reduce false echo:

minimize interfering installati-

ons by changing the polariza-

tion direction

– Chose a more suitable installa-

tion position

– Transverse reflection from an

extraction funnel, amplitude of

the transverse reflection larger

than the level echo

– Direct sensor to the opposite

funnel wall, avoid crossing with

the filling stream

4th measured va-

lue fluctuates around

10 … 20 %

Level

time

0

– Various echoes from an uneven

product surface, e.g. a material

cone

– Check application parameter

"Medium type" and adapt, if

necessary

– Optimize installation position

and sensor orientation

– Reflections from the product

surface via the vessel wall

(deflection)

– Select a more suitable

installation position, optimize

sensor orientation, e.g. with a

swivelling holder

5. measured value

jumps sporadically to

100 % during filling

Level

time

0

– Varying condensation or conta-

mination on the antenna

– Carry out a false signal

suppression or increase false

signal suppression with con-

densation/contamination in the

close range by editing

– With bulk solids use radar sen-

sor with purging air connection

or flexible antenna cover

Measurement error during emptying

Fault description

Error pattern

Cause

Rectification

6th measured value re-

mains unchanged in

the close range during

emptying

Level

time

0

– False echo larger than the level

echo

– Level echo too small

– Remove false echoes in the

close range. Check: Antenna

must protrude out of the socket

– Remove contamination on the

antenna

– Minimize interfering installati-

ons in the close range by chan-

ging the polarization direction

– After removing the false

echoes, the false signal

suppression must be deleted.

Carry out a new false signal

suppression

Advertising