VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual

Page 65

Advertising
background image

65

11 Supplement

VEGAPULS 68 • Profibus PA

36537-EN-130205

Input variable
Measured variable

The measured quantity is the distance between process

fitting of the sensor and product surface. The reference

plane is the seal surface on the hexagon or the lower

side of the flange.

3

4

2

1

Fig. 53: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Antenna length

4 Useful measuring range

Max. measuring range

75 m (246.1 ft)

Recommended meas. range depending on the antenna diameter

Ʋ ø 40 mm (1.575 in)

up to 15 m (49.21 ft)

Ʋ ø 48 mm (1.89 in)

up to 20 m (65.62 ft)

Ʋ ø 75 mm (2.953 in)

up to 40 m (131.2 ft)

Ʋ ø 95 mm (3.74 in)

up to 50 m (164 ft)

Ʋ Parabolic antenna

up to 75 m (246.1 ft)

Output variable
Output signal

digital output signal, format according to IEEE-754

Sensor address

126 (default setting)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Profibus PA profile

3.02

Number of FBs with AI (function blocks

with analogue input)

3

Default values

Ʋ 1. FB

PV

Ʋ 2. FB

SV 1

Ʋ 3. FB

SV 2

Current value

Ʋ Non-Ex and Ex ia instrument

10 mA, ±0.5 mA