Id number, Cyclical data traffic – VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual
Page 71
71
11 Supplement
VEGAPULS 68 • Profibus PA
36537-EN-130205
tically when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA
instrument in the configuration tool.
ID number
Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user
organisation (PNO). This ID number is also included in the name of the GSD file. Optionally to this
manufacturer-specific GSD file, PNO provides also a general so-called profile-specific GSD file. If
the general GSD file is used, the sensor must be set to the profile-specific ident number via the DTM
software. By default, the sensor operates with the manufacturer-specific ID number. When using the
instruments on a segment coupler SK-2 or SK-3, no special GSD files are required.
The following table shows the instrument ID and the GSD names for the VEGAPULS radar sensors.
Device name
Instrument ID
GSD file name
VEGA
Instrument class in
profile 3.02
VEGA
Profile-specific
VEGAPULS WL 61
0x0CDB
0x9702
PS61WL0CDB.GSD PA139702.GSD
VEGAPULS 61
0x0BFC
0x9702
PS610BFC.GSD
PA139702.GSD
VEGAPULS 62
0x0BFD
0x9702
PS620BFD.GSD
PA139702.GSD
VEGAPULS 63
0x0BFE
0x9702
PS630BFE.GSD
PA139702.GSD
VEGAPULS 65
0x0BFF
0x9702
PS650BFF.GSD
PA139702.GSD
VEGAPULS 66
0x0C00
0x9702
PS660C00.GSD
PA139702.GSD
VEGAPULS 67
0x0C01
0x9702
PS670C01.GSD
PA139702.GSD
VEGAPULS SR 68
0x0CDC
0x9702
PS68R0CDC.GSD
PA139702.GSD
VEGAPULS 68
0x0C02
0x9702
PS680C02.GSD
PA139702.GSD
Cyclical data traffic
The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during operati-
on. The below block diagram below shows which data can be accessed by the PLC.