11 Supplement

VEGAPULS 68 • Profibus PA

36537-EN-130205

tically when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA

instrument in the configuration tool.

ID number

Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user

organisation (PNO). This ID number is also included in the name of the GSD file. Optionally to this

manufacturer-specific GSD file, PNO provides also a general so-called profile-specific GSD file. If

the general GSD file is used, the sensor must be set to the profile-specific ident number via the DTM

software. By default, the sensor operates with the manufacturer-specific ID number. When using the

instruments on a segment coupler SK-2 or SK-3, no special GSD files are required.
The following table shows the instrument ID and the GSD names for the VEGAPULS radar sensors.

Device name

Instrument ID

GSD file name

VEGA

Instrument class in

profile 3.02

VEGA

Profile-specific

VEGAPULS WL 61

0x0CDB

0x9702

PS61WL0CDB.GSD PA139702.GSD

VEGAPULS 61

0x0BFC

0x9702

PS610BFC.GSD

PA139702.GSD

VEGAPULS 62

0x0BFD

0x9702

PS620BFD.GSD

PA139702.GSD

VEGAPULS 63

0x0BFE

0x9702

PS630BFE.GSD

PA139702.GSD

VEGAPULS 65

0x0BFF

0x9702

PS650BFF.GSD

PA139702.GSD

VEGAPULS 66

0x0C00

0x9702

PS660C00.GSD

PA139702.GSD

VEGAPULS 67

0x0C01

0x9702

PS670C01.GSD

PA139702.GSD

VEGAPULS SR 68

0x0CDC

0x9702

PS68R0CDC.GSD

PA139702.GSD

VEGAPULS 68

0x0C02

0x9702

PS680C02.GSD

PA139702.GSD

Cyclical data traffic

The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during operati-

on. The below block diagram below shows which data can be accessed by the PLC.