11 Supplement

VEGAPULS 68 • Profibus PA

36537-EN-130205

Fig. 55: VEGAPULS 68: Block diagram with AI FB 1 … AI FB 3 OUT values
TB Transducer Block

FB 1 … FB 3

Function Block

Module of the PA sensors

For the cyclic data traffic, VEGAPULS 68 provides the following modules:

AI FB1 (OUT)

– Out value of the AI FB1 after scaling

AI FB2 (OUT)

– Out value of the AI FB2 after scaling

AI FB3 (OUT)

– Out value of the AI FB3 after scaling

Free Place

– This module must be used if a value in the data telegram of the cyclical data traffic should not

be used (e.g. replacement of temperature and Additional Cyclic Value)

A maximum of three modules can be active. By means of the configuration software of the Profibus

master you can determine the configuration of the cyclical data telegram with these modules. The

procedure depends on the respective configuration software.

Note:

The modules are available in two versions:

Short for Profibus master supporting only one "Identifier Format" byte, e.g. Allen

Bradley

Long for Profibus master only supporting the "Identifier Format" byte, e.g. Siemens

S7-300/400

Examples of telegram configuration

In the following you will see how the modules can be combined and how the appendant data tele-