.3 Wiring plan

1

2

+

( )

(-)

3

4

+

( )

(-)

1

2

3

Fig. 8: Wiring plan VEGADIS 62

1

To the sensor

2

For power supply

3

Coupling for the connection cable to the indicating and adjustment module

5

.4 Connection HART standard

The following illustrations show in a simplified way the use of
VEGADIS

62 in conjunction with a HART sensor. The HART

communication resistance in the signal cable is always required for a
low impedance power supply. It is absolutely necessary to install it
between voltage supply and the VEGADIS 62.

Note:
If the instrument is powered via a VEGAMET signal conditioning
instrument, then the communication resistor is already included in the
signal conditioning instrument. A communication resistor in the signal
cable must not be installed.

~

=

1

2

4

3

Fig. 9: VEGADIS 62 in conjunction with an individual sensor

1

Sensor

2

VEGADIS 62

3

HART resistance > 150 Ω (necessary with low impedance power supply)

4

Voltage supply/Processing