3 wiring plan, 4 connection hart standard – VEGA VEGADIS 62 User Manual
Page 17
5
.3 Wiring plan
1
2
+
( )
(-)
3
4
+
( )
(-)
1
2
3
Fig. 8: Wiring plan VEGADIS 62
1
To the sensor
2
For power supply
3
Coupling for the connection cable to the indicating and adjustment module
5
.4 Connection HART standard
The following illustrations show in a simplified way the use of
VEGADIS
62 in conjunction with a HART sensor. The HART
communication resistance in the signal cable is always required for a
low impedance power supply. It is absolutely necessary to install it
between voltage supply and the VEGADIS 62.
Note:
If the instrument is powered via a VEGAMET signal conditioning
instrument, then the communication resistor is already included in the
signal conditioning instrument. A communication resistor in the signal
cable must not be installed.
~
=
1
2
4
3
Fig. 9: VEGADIS 62 in conjunction with an individual sensor
1
Sensor
2
VEGADIS 62
3
HART resistance > 150 Ω (necessary with low impedance power supply)
4
Voltage supply/Processing
Overview
VEGADIS
62
17
5 Connecting to power supply
36469
-
EN
-120329