7 set up sensors, 1 adjust the sensor, 2 scale the indication – VEGA VEGADIS 62 User Manual

Page 35

Advertising
background image

7

Set up sensors

7

.1 Adjust the sensor

The min./max. adjustment of the connected sensor is carried out via
the menu "Measurement", menu items "Unit", "Measuring range
begin
", "Measuring range end" and if necessary "Measuring range
decimal point
". The entered values are taken over when storing into
the sensor.

Note:
It is recommended to note the transmitted data for the plant
documentation or a possible later correction of the adjustment.

7

.2 Scale the indication

After the min./max. adjustment of the sensor, the actual measured
value is displayed on the VEGADIS 62. The original sensor value, for
example, in "bar" with pressure transmitters or in "m" distance with
radar sensors is converted into the unit set in the menu "Measure-
ment
", menu item "Unit" and is displayed digitally. First of all the
4 … 20 mA current is measured and shown quasianalogue on the
bargraph. This value takes the min./max. adjustment into consider-
ation.

The VEGADIS 62 allows via the unit "USER" a free, application-
specific indication scaling. The VEGADIS 62 acts here as a pure
indicating instrument without HART communication with the connected
sensor.

For the indication scaling proceed as follows:

1

Set in the menu "Configuration", menu item "USER unit" the
requested unit with the available characters.

VEGADIS

62

35

7 Set up sensors

36469

-

EN

-120329

Advertising