Fig. 10: Connection of VEGADIS 62 with low impedance power supply
1
Sensor
2
VEGADIS 62
3
HART resistor > 150 Ω
4
Voltage supply/Processing
5
.5 Connection HART multidrop
The following illustrations show in a simplified way the use of
VEGADIS
62 in conjunction with a HART sensor. The HART
communication resistance in the signal cable is always required for a
low impedance power supply. It is absolutely necessary to install it
between voltage supply and the VEGADIS 62.
Note:
If the instrument is powered via a VEGAMET signal conditioning
instrument, then the communication resistor is already included in the
signal conditioning instrument. A communication resistor in the signal
cable must not be installed.
Connection with low im-
pedance power supply