5 connection hart multidrop – VEGA VEGADIS 62 User Manual

Page 18

Advertising
background image

1

2

+

( )

(-)

3

4

+

( )

(-)

1

2

4

3

Fig. 10: Connection of VEGADIS 62 with low impedance power supply

1

Sensor

2

VEGADIS 62

3

HART resistor > 150 Ω

4

Voltage supply/Processing

5

.5 Connection HART multidrop

The following illustrations show in a simplified way the use of
VEGADIS

62 in conjunction with a HART sensor. The HART

communication resistance in the signal cable is always required for a
low impedance power supply. It is absolutely necessary to install it
between voltage supply and the VEGADIS 62.

Note:
If the instrument is powered via a VEGAMET signal conditioning
instrument, then the communication resistor is already included in the
signal conditioning instrument. A communication resistor in the signal
cable must not be installed.

Connection with low im-
pedance power supply

18

VEGADIS

62

5 Connecting to power supply

36469

-EN

-120329