VEGA VEGADIS 62 User Manual

Page 27

Advertising
background image

In this menu item, the actual measured value is accepted as min.
adjustment for the sensor

6)

This is a zero adjustment to which 0 % of the current output are
assigned. The value accepted hier, shifts the measuring range end!
The difference between measuring range begin and end however
remains.

In this menu item, the integration time for damping the measured value
is entered.

Adjustment range: 0.0 … 999 s

Adjustment of the HART address of the assigned transmitter in
Multidrop mode. With standard current loop operation, this address
must always be set to 0.

Adjustment range: 0 … 15

Adjustment of the unit for the digital indication. First of all the unit
selected in the menu "Measurement", for example m appears.
Furthermore the units from the same unit group such as e.g. mm, cm,
m etc. are available. The measured values are automatically converted
into the selected unit.

If % is selected as unit, then the VEGADIS 62 converts the actual loop
current into a % value relating to the max. loop current. If mA is
selected as a unit, then the actual loop current is displayed in mA.

6)

Is not available with HART multidrop.

Measurement/Live ad-
justment zero point

Measurement/Damping

Measurement/Address

Indication/Unit

VEGADIS

62

27

6 Set parameters

36469

-

EN

-120329

Advertising