5 Connecting to power supply

VEGADIF 65 • 4 … 20 mA/HART

36128-EN-130417

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should

be installed

Tip:

We recommend using VEGA overvoltage arresters B63-48 and

ÜSB 62-36G.X.
In hazardous areas you must take note of the respective regulations,

conformity and type approval certificates of the sensors and power

supply units.

Power supply and current signal are carried on the same two-wire

cable. The voltage supply range can differ depending on the instru-

ment version.
The data for power supply are specified in chapter "Technical data".
Provide a reliable separation between the supply circuit and the

mains circuits according to DIN EN 61140 VDE 0140-1. The VEGA

power supply units VEGATRENN 149A Ex, VEGASTAB 690 as well

as all VEGAMETs and VEGASCANs meet this requirement.
Information:

The signal conditioning instruments VEGAMET 624 and 625 as well

as VEGASCAN 693 have a digital sensor recognition. When con-

necting VEGADIF 65, a software version from 1.92 is required with

the signal conditioning instrument. For software update move under

"www.vega.com/downloads" to "Software".
Keep in mind the following additional factors that influence the operat-

ing voltage:

Output voltage of the power supply unit can be lower under nomi-

nal load (with a sensor current of 20.5 mA or 22 mA in case of fault

message)

Influence of additional instruments in the circuit (see load values in

chapter "Technical data")

The instrument is connected with standard two-wire cable without

screen. If electromagnetic interference is expected which is above the

test values of EN 61326 for industrial areas, screened cable should

be used.
Use cable with round cross-section. A cable outer diameter of

5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.

If you are using cable with a different diameter or cross-section,

exchange the seal or use a suitable cable gland.
We generally recommend the use of screened cable for HART multi-

drop mode.