VEGA VEGADIF 65 4 … 20 mA_HART User Manual
Page 86
86
11 Supplement
VEGADIF 65 • 4 … 20 mA/HART
36128-EN-130417
Load
see diagram
1000
750
500
250
12
18
16
14
20
22
24
26
28
30
32
34
36
Ω
V
4
1
2
3
Fig. 61: Voltage diagram
1 HART load
2 Voltage limit Ex-ia instrument
3 Voltage limit non-Ex/Ex-d instrument
4 Operating voltage
Electrical protective measures
Protection rating
Ʋ Housing, standard
IP 66/IP 67
Ʋ Aluminium and stainless housing
(optionally available)
IP 68 (1 bar)
Ʋ Process component in IP 68 version IP 68 (25 bar)
Ʋ External housing
IP 65
Overvoltage category
III
Protection class
II
Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully
noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"
and "serial number search" as well as via "Downloads" and "Approvals".