VEGA VEGADIF 65 4 … 20 mA_HART User Manual
Page 35
35
5 Connecting to power supply
VEGADIF 65 • 4 … 20 mA/HART
36128-EN-130417
4. Remove approx. 10 cm of the cable mantle, strip approx. 1 cm
insulation from the individual wires
5. Insert the cable into the sensor through the cable entry
6. Lift the opening levers of the terminals with a screwdriver (see
following illustration)
7. Insert the wire ends into the open terminals according to the wir-
ing plan
8. Press down the opening levers of the terminals, you will hear the
terminal spring closing
9. Check the hold of the wires in the terminals by lightly pulling on
them
10. Connect the screen to the internal ground terminal, connect the
outer ground terminal to potential equalisation
11. Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
12. Screw the housing cover back on
The electrical connection is hence finished.
Fig. 34: Connection steps 6 and 7
Proceed as follows:
1. Loosen the four screws on the housing base with an Allen key
size 4
2. Remove the mounting plate from the housing socket
IP 68 version with exter-