6 Adjustment with the display and adjustment module PLICSCOM

VEGADIF 65 • 4 … 20 mA/HART

36128-EN-130417

For an adjustment with filling, simply enter the actual measured value

indicated at the bottom of the display.
The min. adjustment is finished.

For the max. adjustment with density, a filling of the vessel is not

necessary. The numeric examples are stated in chapter Mounting,

Measurement setup, Density and interface of this instructions manual.
Proceed as follows:
1. Edit the % value in the menu item "Max. adjustment" with [OK].

100.00 %
=
0.1000 bar
0.0000 bar

Information:

If the instrument has not yet been adjusted, the displayed pressure for

100 % corresponds to the nominal measuring range of the sensor (in

the above example 100 mbar).
2. Set the requested value with [->] and [OK], for example 0.0 %.
3. Confirm with [OK] and edit the requested mbar value.
4. Set the requested value with [+] and [->], for example 35.3 mbar.
5. Confirm with [OK] and move to the menu overview with [ESC].
For an adjustment with filling, simply enter the actual measured value

indicated at the bottom of the display.
The max. adjustment is finished.

Proceed as follows:
1. Edit the bar value in the menu item "Min. adjustment" with [OK].

Min. adjustment
0.00 %

DP

- +

=
0.0000 bar
0.0000 bar

2. Set the requested bar value with [+] and [->].
3. Confirm with [+] and move to max. adjustment with [->].
For an adjustment with flow, simply enter the actual measured value

indicated at the bottom of the display.
Information:

The VEGADIF 65 is also suitable for bidirectional flow measurement

(flow in both directions). The selection is carried out in the menu item

"Linearization curve". With the bidirectional flow measurement, the

min. adjustment value must be equal to the negative max. adjustment

value.
Example: Max. adjustment value +100 mbar, as min. adjustment

value, -100 mbar must hence be entered.
The min. adjustment is finished.

Proceed as follows:

Max. adjustment with

density

Min. adjustment with flow

Max. adjustment with flow