5 Connecting to power supply

VEGADIF 65 • 4 … 20 mA/HART

36128-EN-130417

3

2

1

Fig. 35: Components of the external housing
1 Screws

2 Wall mounting plate

3 Cable gland

3. Loop the connection cable through the cable entry on the housing

base

1)

Information:

The cable gland can be mounted in three positions each displaced

by 90°. Simply exchange the cable gland against the blind plug in the

suitable thread opening.
4. Connect the wire ends as described under "Single/Double cham-

ber housing" according to the numbering

5. Connect the screen to the internal ground terminal, connect the

outer ground terminal above on the housing to potential equalisa-

tion

6. Tighten the compression nut of the cable entry. The seal ring must

completely encircle the cable

7. Attach the mounting plate again and tighten the screws
The electrical connection of the sensor to the external housing is

finished.

1)

The connection cable comes pre-assembled. If necessary, shorten it to the

requested length, cut the breather capillaries clean. Remove approx. 5 cm of

the cable mantle, strip approx. 1 cm insulation from the ends of the individual

wires. After shortening the cable, fasten the type plate with support back on

the cable.