Wha-gw, Operation, 85 modbus specific status hart device status – VEGA WHA-GW-WIRELESSHART GATEWAY User Manual

Page 85

Advertising
background image

WHA-GW-*

Operation

22

1981

2011

-0

7

85

Modbus specific status

HART device status

Modbus Register

Value

Description

Format

Sub-device
Index
(CMD 84)

30013

30014

AI

Primary Variable
(loop current, mA unit)

32-bit floating
point

1

30015

30016

PV

Primary Variable
(device-specific unit)

30017

30018

SV

Secondary Variable
(device-specific unit)

30019

30020

TV

Tertiary Variable
(device-specific unit)

30021

30022

QV

Quaternary Variable
(device-specific unit)

30023

ModStat

Modbus Specific Status *

16-bit
unsigned
integer

30024

DevStat

HART Device Status *

30025

30026

AI

Primary Variable
(loop current, mA unit)

32-bit floating
point

2

30027

30028

PV

Primary Variable
(device-specific unit)

30029

30030

SV

Secondary Variable
(device-specific unit)

30031

30032

TV

Tertiary Variable
(device-specific unit)

30033

30034

QV

Quaternary Variable
(device-specific unit)

30035

ModStat

Modbus Specific Status *

16-bit
unsigned
integer

30036

DevStat

HART Device Status *

* For a detailed description refer to the following tables.

Bit

Parameter

Description

0x01 (LSB**)

Cache validity

Set to "1" when the HART Command 3
cache of the device is "empty".

0x02 (LSB**)

Identification
ongoing

Set to "1" when the Gateway is performing
a device identification procedure.

** LSB = least significant bit

Bit

Parameter

Description

0x80

Device malfunction

The device detected a serious error or
failure that compromises device operation.

0x40

Configuration
changed

An operation was performed that changed
the device's configuration.