Appendix a, Read only register list – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual

Page 10

Advertising
background image

8

GE Zenith Controls

MX150/MX250 Series Modbus Network Card (71R-2200)

Appendix A

(cont’d)

Read Only Register List

Holding Reg.

Bit Coil Description

Value

40068

Timer ID 1

0 97 Unused

1 98 Unused

2 99 A6/A62 Timer Running

1 = Running

3 100 T Timer Running

1 = Running

4 101 DT Timer Running

1 = Running

5 102 T3/W3 Timer Running

1 = Running

6 103 W Timer Running

1 = Running

7 104 DW Timer Running

1 = Running

40069

T or W Timer Countdown Value

Seconds

40070

T3/W3 Timer Countdown Value

Seconds

40071

A6/A62 Timer Countdown Value

Seconds

40072

MX Firmware Revision

Ver = Value/10

40073

Modbus Card Firmware Revision

Ver = Value/100

40074

Unused

40075

Unused

40076

Unused

40077

Most Recent Event Pointer

40082

Unused

40083

Unused

40099

System Time – Day of Week

Holding Reg.

Bit Coil Description

Range

Notes

40102

Exerciser

Record

– Hour

0 - 23

40103

Exerciser

Record

– Minute

0 - 59

40104

Exerciser

Record

– Month

1 - 12

Not writeable for Daily

or

Weekly

Exercisers

40105

Exerciser

Record

– Day of Month

1 - 31

Max val. depends on month, year

Not writeable for Daily

or

Weekly

Exercisers

40106

Exerciser

Record

– Day of Week

1 = Sun., 7 = Sat.

Writeable for Weekly Exercisers Only

40107

Exerciser

Record

– Ex. Duration

0 - 600 minutes

40108

Exerciser

Record

– Load/No Load

1 = Load, 0 = No Load

Writeable ONLY if Factory

Configured for Load Exercisers

40109

Unused

40110

Exerciser Schedule Selection

0 = Off

1 = Daily (1 Day)

2 = Weekly (7 Day)

3 = Bi-Weekly (14 Day)

4 = 4 Week (28 Day)

5 = Calendar (365 Day)