Appendix g, Modbus protocol illustration, Cont’d) – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual

Page 22: The requested, And a logical ‘0’ requests it to be, 00 hex) will set the coil, And the value zero will turn it, Coil 71, Hex) in slave device 17

Advertising
background image

20

GE Zenith Controls

MX150/MX250 Series Modbus Network Card (71R-2200)

Write Multiple Coils (Function Code 15)
Forces each coil in a sequence of coils to either

ON

or

OFF

. The requested

ON

/

OFF

states are specified by con-

tents of the query data field. A logical ‘1’ in a bit position
of the field requests the corresponding coil to be

ON

and a

logical ‘0’ requests it to be

OFF

. Coils are addressed

starting at 0. For examples coil 1 is addressed as 0.

Query

The following example is a request to force a series of six-
teen coils starting at coil 41 (addressed as 40, or 28 hex)
in slave device 9.

The query data contents consist of two bytes: 3

C

9

B

hex

(0011 1100 1001 1011 binary). The binary bits corre-
spond to the coils in the following way:

The first byte sent (3

C

hex) addresses coils 41-48, with

the least significant bit addressing coil 41. The second
byte sent (9

B

hex) addresses coils 49-56, with the least

significant bit addressing coil 49.

Response

The slave responds with its address, function code, number
of data bytes, and the data. The contents of the registers
requested (data) are two bytes each. The first byte includes
the high order bits and the second, the low order bits.

Register 40006 , Normal Voltage Ph1-Ph2, has a value of
118 (76 hex) and register 40007, Normal Voltage Ph2-
Ph3 has a value of 120 (78 hex).

Appendix G

(cont’d)

Modbus Protocol Illustration

(cont’d)

Slave

Address

08h

Figure G4 – Read Holding Register Response Message

Function

Code

Byte

Count

High

Order

Data

Low

Order

Data

High

Order

Data

Error

Check Field

(LRC or CRC)

03h

04h

00h

76h

00h

Low

Order

Data

78h

Write Single Coil (Function Code 05)
This function forces a single coil either

ON

or

OFF

. A value

of 65,280 (

FF

00 Hex) will set the coil

ON

and the value

zero will turn it

OFF

; all other values are illegal and will not

affect that coil.

Query

Figure G5 is an example of a request to slave number 3
to turn

ON

coil 71.

Slave

Address

03h

Figure G5 – Write Single Coil Query Message

Function

Code

Starting

Address

High

Order

Starting

Address

Low

Order

Data

High

Order

Data

Low

Order

Error

Check Field

(LRC or

CRC)

05h

00h

46h

FF

h

00h

Response

The slave’s normal response to the Write Single Coil
query is to return the original message after the coil state
has been altered.

Slave

Address

03h

Figure G6 – Write Single Coil Response Message

Function

Code

Starting

Address

High

Order

Starting

Address

Low

Order

Data

High

Order

Data

Low

Order

Error

Check Field

(LRC or

CRC)

05h

00h

46h

FF

h

00h

Slave

Address

11h

Figure G7 – Write Single Holding Register Query Message

Function

Code

Starting

Address

High

Order

Starting

Address

Low

Order

Data

High

Order

Data

Low

Order

Error

Check Field

(LRC or

CRC)

06h

00h

28h

00h

5

C

h

Response

The slave’s response to the Write Single Holding
Register query is to return the original message after the
registers have been altered.

Slave

Address

11h

Figure G8 – Write Single Holding Register Response Message

Function

Code

Starting

Address

High

Order

Starting

Address

Low

Order

Data

High

Order

Data

Low

Order

Error

Check Field

(

LRC

or

CRC

)

06h

00h

28h

00h

5

C

h

Coil:

48 47 46 45 44 43 42 41

56 55 54 53 52 51 50 49

Bit:

0

0

1

1

1

1

0

0

1

0

0

1

1

0

1

1

Write Single Holding Register (Function Code 06)
This function allows the master to modify the contents
of one holding register.

Query

Figure G7 is an example of a request to preset register
40041 (Normal Pickup Voltage) to 92 (00 5

C

hex) in

slave device 17.

Slave

Address

09h

Figure G9 – Write Multiple Coils Query Message

Function

Code

0Fh

Starting

Address

High

Order

00h

Starting

Address

Low

Order

28h

Number

of Coils

High

Order

00h

Number

of Coils

Low

Order

10h

Byte

Count

02h

Data

High

Order

3

C

h

Data

Low

Order

9

B

h

Error

Check

Field

(

LRC

or

RC

)