Appendix b, Read/write register list – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual

Page 16

Advertising
background image

14

GE Zenith Controls

MX150/MX250 Series Modbus Network Card (71R-2200)

Appendix B

(cont’d)

Read/Write Register List

Holding Reg. Bit Coil Description

Range

Notes

HR 40094 - 40098 MUST ALL be written with a Write Multiple Holding Register Command

40094

System

Time

– Hour

0 - 23

40095

System

Time

– Minute

0 - 59

40096

System

Time

– Day

1 - 31

Max val. depends on month, year

40097

System

Time

– Month

1 - 12

40098

System

Time

– Year

0 - 255, 0 = Year 2000

40100

Daylight Savings Time

1 = ATS follows DST

HR 40101 - 40109 MUST ALL be written with a Write Multiple Holding Register Command

HR's listed as "Not Writeable" under certain conditions must be written as zeros

HR40101-40110 are for CDP Programmable Exercisers Only

40112

System Busy Control

0 113 Command to Bypass In-Phase Monitor 1 = Bypass In-Phase Monitor

1 114 Confirm Bypass In-Phase Monitor

1 = Confirm

2

115

Unused

3

116

Unused

4

117

Unused

5

118

Unused

6

119

Unused

7

120

Unused

40113

Net Control 2

0 121 Bypass Pending Exerciser

1 = Bypass

1 122 Cancel Exerciser Bypass

1 = Cancel Bypass

2

123

Unused

3

124

Unused

4

125

Unused

6

127

Unused

7

128

Unused