Appendix a, Read only register list – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual

Page 9

Advertising
background image

GE Zenith Controls

7

MX150/MX250 Series Modbus Network Card (71R-2200)

Appendix A

(cont’d)

Read Only Register List

Holding Reg.

Bit Coil Description

Value

40025

S1 Voltage (Phase A-B), Raw A/D

Raw A/D Value - See Note 1

40026

S1 Voltage (Phase B-C), Raw A/D

Raw A/D Value - See Note 1

40027

S1 Voltage (Phase C-A), Raw A/D

Raw A/D Value - See Note 1

40028

S2 Voltage (Phase A-B), Raw A/D

Raw A/D Value - See Note 1

40029

S2 Voltage (Phase B-C), Raw A/D

Raw A/D Value - See Note 1

40030

S2 Voltage (Phase C-A), Raw A/D

Raw A/D Value - See Note 1

40031

S1 Period Count

Raw Value - See Note 2

40032

S2 Period Count

Raw Value - See Note 2

40049

Total S1 Fails

40050

Total Transfers to S2

40051

Days Powered Up

40052

Time S1 Available (MSR)

Hours

40053

Time S1 Available (LSR)

Hours

40054

Time S2 Available (MSR)

Hours

40055

Time S2 Available (LSR)

Hours

40056

Unused

40057

Unused

40058

Unused

40059

Unused

40060

Unused

40061

Unused

40062

Unused

40063

Exerciser Schedule Status

0 81 Exerciser Type

1 = Clock, 0 = Timer

1 82 Load/No Load Exerciser (Timer Exerciser Only)

1 = Load

2 83 User can set load exercises (Clock Exerciser Only) 1 = Yes

3 84 Unused

4 85 Unused

5 86 Unused

6 87 Unused

7 88 Unused

[15:8]

Timer Exerciser Run Duration

Minutes

40064

MX Status 3

0 89 Exerciser Pending

1 = Exerciser Pending

1 90 Exerciser Bypassed

1 = Exerciser Bypassed

2 91 Unused

3 92 Unused

4 93 Unused

5 94 Unused

6 95 Unused

7 96 Unused

40065

Unused

40066

Unused

40067

Unused

Advertising