Appendix a, Read only register list – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual

Page 14

Advertising
background image

12

GE Zenith Controls

MX150/MX250 Series Modbus Network Card (71R-2200)

2.

Registers 40031 and 40032 contain unscaled
frequency values. In order to obtain a full-scale
frequency value, use the following formula:
Scales Frequency + (20,000,000 / Period Count)

Notes:

1.

Registers 40025 - 40030 contain unscaled voltage
values In order to obtain a full-scale voltage value,
use the following formula:
Voltage = (A/D Raw Value / 192) x
Full Scale Voltage (Register 40021)

Timer Value

P 111b
W-W3, Unbypassed

110b

W-W3, YE bypassed

101b

T-T3, Unbypassed

011b

Y-T3, YN bypassed

010b

U 000b

Reason Code

Description

0 S1

Fail

1 S2

Fail

2

S1 Phase Imbalance

3

S2 Phase Imbalance

4 S2

Start

5 S2

Stop

6 Sync

Fail

7 Load

Shed

8 ATS

Inhibit

9 Phase

Rotation

10 Remove

Test

11 Local

Test

12 S1-S2

Volt.

Imbalance

13

S1-S2 Freq. Imbalance

14

CT Xfr S1>S2

15

CT Xfr S2>S1

16 Xfr

S1>S2

17 Xfr

S2>S1

18
19
20 No

Xfr

21 OLC
22 STE

23

S1 UV Fail

24

S1 OV Fail

25

S1 UF Fail

26

S1 OF Fail

27

S2 UV Fail

28

S2 OV Fail

29

S2 UF Fail

30

S2 OF Fail

31 S1

Restore

32

S2 to Open

33 Exerciser
34 Remote

Test

Network

35 Remote

Inhibit

36 Local

Inhibit

37 S2

Avail

38 S2

Off

Appendix A

(cont’d)

Read Only Register List

Advertising