Appendix a, Read only register list – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual

Page 8

Advertising
background image

6

GE Zenith Controls

MX150/MX250 Series Modbus Network Card (71R-2200)

Appendix A

(cont’d)

Read Only Register List

Holding Reg.

Bit Coil Description

Value

40005

Timer Countdown Value

Seconds

40006

S1 Voltage (Phase A-B)

Volts

40007

S1 Voltage (Phase B-C)

Volts

40008

S1 Voltage (Phase C-A)

Volts

40009

S2 Voltage (Phase A-B)

Volts

40010

S2 Voltage (Phase B-C)

Volts

40011

S2 Voltage (Phase C-A)

Volts

40012

Unused

40013

S1 Frequency

Freq Value = scaled value/10

40014

Unused

40015

S2 Frequency

Freq Value = scaled value/10

40016

Unused

40017

Total Transfers to S1

40018

Unused

40019

Serial Number (MSR)

40020

Serial Number (LSR)

40021

Nominal Full-Scale Voltage

40022

MX Network Configuration 0

0 41 Unused

1 42 Unused

2 43 Unused

3 44 Unused

4 45 Unused

5 46 Closed Transition Configured

1 = Configured

6 47 In-Phase Monitor Configured

1 = Configured

7 48 ATS Type

1 = Delay, 0 = Standard

40023

MX Network Configuration 1

0 49 S12 Auto/Manual Option

1 = Configured

1 50 S5 Auto/Manual Bypass Option

1 = Configured

2 51 Phase Sequence Check Option

1 = Configured

3 52 S2 Overfrequency Option

1 = Configured

4 53 S2 Overvoltage Option

1 = Configured

5 54 S1 Overfrequency Option

1 = Configured

6 55 S1 Underfrequency Option

1 = Configured

7 56 S1 Overvoltage Option

1 = Configured

40024

MX Network Configuration 2

0 57 Phase Imbalance Configured

1 = Configured

1 58 Unused

2 59 Closed Transition Configured

1 = Configured

3 60 Pre-Load Disconnect

1 = Configured

4 61 Post-Load Disconnect

1 = Configured

5 62 Open Loop Transfer Option

1 = Configured

6 63 Unused

7 64 Controller Type

1 = MX150/250, 0 = MX200