Appendix g, Modbus protocol illustration, Cont’d) – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual

Page 23

Advertising
background image

GE Zenith Controls

21

MX150/MX250 Series Modbus Network Card (71R-2200)

Appendix G

(cont’d)

Modbus Protocol Illustration

(cont’d)

Response

The response from the slave is an echo of the slave
address, function code, starting address and number
of coils forced.

Slave

Address

09h

Figure G10 – Write Multiple Coils Response Message

Function

Code

Starting

Address

High Order

Starting

Address

Low Order

Number

of Coils

High

Order

Number

of Coils

Low

Order

Error

Check Field

(

LRC

or

CRC

)

0Fh

00h

28h

00h

10h

Write Multiple Holding Registers (Function Code 16)
Presets values into a sequence of holding registers.

Query

The following is an example to preset two registers
starting at 40034 (

W

-Time) to 9 hex (9 seconds) and 40035

(

W

3-time) to 32 hex (50 seconds), in slave device 17.

Slave

Address

11h

Figure G11 – Write Multiple Registers Query Message

Function

Code

10h

Starting

Address

High

Order

00h

Starting

Address

Low

Order

21h

Number

of Regs

High

Order

00h

Number

of Regs

Low

Order

02h

Byte

Count

04h

Data

High

Order

00h

Data

Low

Order

09h

Data

High

Order

00h

Data

Low

Order

32h

Error

Check

Field

(LRC or

CRC

)

Response

The response from the slave is an echo of the slave
address, function code, starting address and number
of registers to be loaded.

Slave

Address

11h

Figure G12 – Write Multiple Registers Response Message

Function

Code

Starting

Address

High

Order

Starting

Address

Low

Order

Number

of Regs

High

Order

Number

of Regs

Low

Order

Error

Check Field

(

LRC

or

CRC

)

10h

00h

21h

00h

02h