Operation, Setting system time, Operation with in-phase monitor – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual

Page 6: Bypass pending exerciser, Cancel bypass, Operation under battery backup

Advertising
background image

4

GE Zenith Controls

MX150/MX250 Series Modbus Network Card (71R-2200)

Operation

Setting System Time

Holding Registers 40094 through 40099 are provided to

control and report the status of the controller’s System

Time. Reading Holding Register 40094 through 40099

will report the current Hour, Minute, Day, Month, Year,

and Day of Week to which controller’s internal clock is

currently set.

Writing the System Time Holding Registers

Holding Registers 40094 through 40098 must be written

using a Write Multiple Holding Register Command

(Function Code 16). This is to ensure that the data con-

tained in these registers is a complete ordered set. Any

attempt to write Holding Registers 40094, 40095, 40096,

40097, or 40098 with a Write Single Holding Register

Command (Function Code 6), or a Write Multiple

Holding Register Command (Function Code 16) that

does not include the entire range of 40094 - 40098, will

result in an Illegal Data Address exception response

from the Modbus Card.

Note: Holding Register 40099, “System Time-Day of

Week” is Read Only. The value of this register is auto-

matically computed and updated by the controller,

based on the calendar date.

Operation with In-Phase Monitor

Special consideration is required if the controller is con-

figured with the In-Phase Monitor. Most Modbus net-

work data and control are unavailable while the In-Phase

Monitor is waiting for phase synchronization. The

Modbus Network Card will return a “Slave Device Busy”

exception code (06h) to all Modbus queries, except for

queries to the System Busy Status Register (Holding

Register 40112) or the System Busy Control Register

(Holding Register 40113).

If the Modbus Network Card returns a Slave Device Busy

exception code, information about the source of the

busy condition may be available in the System Busy

Status Register (Holding Register 40112). If Bit 0 of the

System Busy Status Register (Coil 105) is set to one, the

controller is busy waiting for phase synchronization.

If the controller is busy waiting for phase synchroniza-

tion, the In-Phase Monitor may be bypassed over the

Modbus network by performing the following sequence:

Warning: EXTREME CAUTION must be used when

bypassing the In-Phase Monitor! Transferring between

sources that are not in phase synchronization may cause

unexpected operation, resulting in damage to plant

equipment and personnel.

1. Set Bit 0 of the System Busy Control Register (Coil

113) to one. This is a request by the Modbus user to

bypass the In-Phase Monitor.

2. Once an In-Phase Monitor bypass has been requested,

and the controller has been waiting for phase synchro-

nization for more than one minute, the controller will

request confirmation of the In-Phase Monitor bypass.

This request is indicated by a one in Bit 1 of the System

Busy Status Register (Coil 106).

3. To confirm the request to bypass, set Bit 1 of the

System Busy Control Register (Coil 114) to one.

The controller will bypass the In-Phase Monitor.

Note: The In-Phase Monitor bypass feature is an inter-

locked command-and-confirm mechanism. The Modbus

Card will not allow the Confirm Bypass control bit

(Coil 114) to be set before the controller has set Ready

to Confirm Bypass status bit (Coil 106). If a write request

is received to set Coil 114 before the controller has set

Coil 106, an Illegal Data Value error code will be returned.

Bypass Pending Exerciser

Bit 0 (Coil 121) is the Bypass Pending Exerciser bit.

The MX Platform performs a logic-OR with this bit and

the BPASS EXER key on the HMI. A 1 in Bit 0 bypasses

the pending exerciser; a 0 does nothing.

Cancel Bypass

Bit 1 (Coil 122) is the Cancel Bypass bit. The MX

Platform performs a logic-OR this bit with the CANCL

BPASS key on the HMI. A 1 in Bit 1 cancels the Bypass

Pending Exerciser. A 0 in this bit position does nothing.
The Bypass Pending Exerciser Bit works different,

between a Timer Exerciser and Clock Exerciser,

depending on the state of Exerciser Type (Holding

Register 40063, Bit 0, Coil 81). When Coil 81 = 0 (Timer

Exerciser), if Coil 121 is set to 1, the Timer Exerciser

will be bypassed until the Cancel Bypass Bit (Coil 122)

is set to 1. When Coil 81 = 1 (Clock Exerciser), if Coil

121 is set to 1, only the exerciser that is pending at the

time gets bypassed, and the exerciser only gets bypassed

once. The Controller waits for Coil 121 to reset to a 0

before a subsequent bypass can be performed.

Operation Under Battery Backup

The controller can be powered from an external 12-volt

battery in the event that neither S1 nor S2 are available.

While the controller is on external battery backup,

data will still be available over the Modbus Network

as noted below.
While the controller is running on external battery

backup, data regarding ATS position and limit switch

inputs may be invalid if both S1 and S2 sources are lost.

Therefore, if Bits 6 and 7 of Holding Register 40001,

or Coils 7 and 8, are both zero, the following Modbus

network data may not be reliable:

• Automatic Transfer Relay –

Holding Register 40001, Bit 0 or Coil 1

• SN Limit Switch –

Holding Register 40002, Bit 0 or Coil 9

• SE Limit Switch –

Holding Register 40002, Bit 1 or Coil 10

• SNO Limit Switch –

Holding Register 40002, Bit 2 or Coil 11

• SEO Limit Switch –

Holding Register 40002, Bit 3 or Coil 12

• S1 Position Status –

Holding Register 40004, Bit 9 or Coil 34

• S2 Position Status –

Holding Register 40004, Bit 10 or Coil 35

Advertising