GE Industrial Solutions EntelliGuard E Circuit Breaker User Manual
Page 17
©2012 General Electric All Rights Reserved
17
CLOSING PROCEDURE
Pull the charging handle out and down to charge the
closing springs (requires approximately 10 pumps of
the handle to fully charge).
If a motorized spring charging unit is installed, the
springs will be automatically charged as soon as the
motor is energized.
Pressing the CLOSE pushbutton or energizing the
closing coil (if installed) will close the circuit breaker.
CONDITIONS WHEN CLOSING CANNOT OCCUR
The OPEN button is in a depressed position.
The trip unit is not installed.
If racking handle is inserted, remove it.
The breaker is positioned anywhere between
CONNECTED, TEST and DISCONNECTED positions.
Trip unit reset button is protruding from the front
cover. Press the reset button.
A network interlockis installed and the SET coil is
activated.
A key interlock is operating on the breaker.
CIRCUIT BREAKER OPENING PROCEDURE
Press the OPEN pushbutton or energize the shunt
trip coil (if installed).
Tripping under fault conditions will be automatic
from the EntelliGuard Messenger.
Table 4.2. Cassette Operating Positions
Circuit Breaker
Position in the
Cassette
Primary
Disconnects
Secondary
Disconnects
Circuit Breaker Functionality
Circuit Breaker
Door Position
CONNECTED engaged engaged
circuit breaker may be operated both mechanically or electrically
ready for service
closed
TEST disengaged
engaged
circuit breaker may be operated both mechanically or electrically
circuit breaker and control circuit operations may be tested and
verified
closed
DISCONNECTED disengaged disengaged
circuit breaker may be operated only mechanically
circuit breaker may not be removed from the circuit breaker
compartment
closed
WITHDRAWN disengaged disengaged
circuit breaker may be operated only mechanically
circuit breaker may be removed from the circuit breaker
compartment
open