Danger, Warning, Caution – GE Industrial Solutions EntelliGuard E Circuit Breaker User Manual

Page 18: Notice

Advertising
background image

EntelliGuard® E Circuit Breaker

DEH-41526

18

©2012 General Electric All Rights Reserved

SECTION 5 – LOCKS AND INTERLOCKS

DANGER

ELECTROCUTION
Ensure the circuit breaker has been tripped, indicating
OFF, and the main springs are fully discharged before
installing locks and interlocks.
Failure to comply with these instructions will result
in death or serious injury.

WARNING

IMPROPER INSTALLATION, OPERATION AND
MAINTENANCE
Ensure only qualified personnel install, operate,
service and maintain all electrical equipment.
Failure to comply with these instructions could
result in death or serious injury.

WARNING

PERSONAL INJURY

 Avoid risk of injury from moving parts while

handling the circuit breaker.

Failure to comply with these instructions could

result in death or serious injury.

CAUTION

PRODUCT DAMAGE
 Ensure the circuit breaker and its accessories are

always used within their designated ratings.

Failure to comply with these instructions may result

in product damage.

GENERAL INFORMATION

NOTICE

Ensure all padlocks are scissor compatible.


A variety of locks and interlock accessories are available.
The operation of most of these accessories is described in
this section.

CIRCUIT BREAKER FRONT PANEL LOCKING

Padlock or Scissor Lock for Breaker Trip Free Condition
1. While pressing the OFF pushbutton, pull out the

padlock lever.

2. Ensure padlock shaft diameter is 3 mm to 9.5 mm.
3. Insert padlock hasp (Fig. 5.1).


Figure 5.1. Padlock for Breaker Trip Free Condition

DRAWOUT CASSETTE FRONT PANEL LOCKING

Security Locking
This function locks the entry of the racking handle in the
crank insertion hole of the cassette front panel when the
padlock is installed when circuit breaker in the
DISCONNECTED/ CONNECTED position. Up to three
padlocks (shaft diameter of 3 mm to 9.5 mm) may be
installed for additional security (Fig. 5.2).

Figure 5.2. Circuit Breaker Security Padlocking Location

A Security Locking Bar


1. Ensure the position indicator shows the

DISCONNECTED/CONNECTED position.

2. Remove the racking handle from the operating

position.

3. Pull the locking bar until the locking eye is exposed

and hold while inserting the padlock shaft (Fig. 5.3).


Figure 5.3. Padlock Insertion and Lock-Out on the
Security Locking Bar

Isolation Shutters Locking (If Installed)

This function locks the operation of the safety shutters
when the padlock is installed on the security locking

A