Table 6.4. Remote Operation Coil Combination

Combination

Coil Position on Fascia (from left)

1 2

3

1

NI SET

NI RESET

CC

ST

Auxiliary Switches

Auxiliary switches indicate breaker main contact position.
They change their state in the same time sequence as the
breaker main contacts. See Table 6.6 for rating.


Table 6.5. Auxiliary Switches

Contact Configuration Cat.

No.

Power rated (3NO+3NC)

GAUX3R


Table 6.6. Auxiliary Switch Ratings and Secondary
Disconnect Points

Contact Configuration

Power Rated Cat. No.

Power rated(3NO+3NC)

A14 - A25

GAUX3R

Circuit Breaker - Key Interlock Facility

This option provides factory-installed interlocking devices for
installation between separate circuit breakers (baseplates and
mechanism). This safeguard ensures that a circuit breaker
cannot be closed unless the dedicated key has been inserted
and secured within the lock. Circuit breakers accept ready-to-fit
interlocking device kits such as Kirk for installation between
related, separate circuit breakers (Table 6.7).

NOTE: Locks and keys are not supplied by GE. Please order
separately from your local supplier.

Table 6.7. Key Interlocks and Door Interlocks

Description Catalog

Number

Baseplate and mechanism for Kirk Key
locks (breaker mounted)

GBKRKR

Mechanism for Kirk key cassette interlock
(cassette mounted)

GCKRKR

Door interlock (left side)

GLHD

Door interlock (right side)

GRHD

Carriage Position Switch (TOC)
Available as an option for mounting within the base of the
cassette/substructure, the carriage position switch provides
changeover contacts for electrical indication of the circuit
breaker status: CONNECTED & TEST. This option is in addition
to the mechanical indicators, which are fitted as standard.
When installed, the carriage switch is IP2X protected and
includes wiring to a terminal block located on the left side of
the cassette (Table 6.8).

Table 6.8. Carriage Position Switches

Switch Configuration

Catalog Number

1 NO/NC switch per position

GCPS4R

Bell Alarm with Lockout
The bell alarm provides remote indication that the circuit
breaker has opened because of an electrical fault. The
Lockout feature is integral to the trip unit. When a Bell Alarm
is supplied with the breaker, the trip unit dial is set and
locked to the manual position. In order to re-close the
breaker, the Lockout button must be pushed in/reset on the
trip unit 1-Form C contact (Table 6.9).
Table 6.9. Bell Alarm Switches

Switch Configuration

Cat. No.

One single pole, double throw switch
(1-Form C contact)

GBAT1R

Charging Spring Status Indicator
Factory-installed on the motor, this auxiliary switch indicates
that the circuit breaker is charged and is standard with the
spring-charging motor.

Secondary Disconnects (Factory-installed/Field
Installable)
Inputs and outputs to the circuit breaker are wired through
secondary disconnects located on the top of the breaker.
The plug-style secondary disconnects engage mating
disconnects in the breaker cubicle when the breaker is in the
TEST or CONNECT position. Up to 39 points are available so
that all breaker accessories can be wired to dedicated
disconnect points. See Table 6.10 for block location and
Table 6.11 for secondary disconnect parts.

Table 6.10. Block Location

Top Disconnect

Block B

Block A

circuit breaker/cradle
viewed from the front


Table 6.11. Secondary Disconnect Parts

Breaker Type

Mounting

Number of

Poles

Cat. No.

Drawout

Top

39 pole set

GSDWSR

 Set contains both the male and female sides of the secondary

disconnect.

 Drawout kits include the metal bracket for connections to the cassette.