SECTION 7 – ACCESSORIES INSTALLATION

DANGER

ELECTROCUTION
Ensure the circuit breaker has been tripped, indicating
OFF, and the main springs are fully discharged before
installing accessories.
Failure to comply with these instructions will result
in death or serious injury.

WARNING

IMPROPER INSTALLATION, OPERATION AND
MAINTENANCE
Ensure only qualified personnel install, operate, service
and maintain all electrical equipment.
Failure to comply with these instructions could
result in death or serious injury.

WARNING

PERSONAL INJURY

 Avoid risk of injury from moving parts while

handling the breaker.

Failure to comply with these instructions could

result in death or serious injury.

CAUTION

PRODUCT DAMAGE
 Ensure circuit breaker and its accessories are

always used within their designated ratings.

Failure to comply with these instructions may result

in product damage.

CIRCUIT BREAKER FRONT COVER REMOVAL

Required for most accessory installation.
1. Remove the six mounting screws (Fig. 7.1).
Figure 7.1. Front Cover

2. Pull the charging handle while easing the cover

upwards .


MOTOR OPERATOR - SPRING CHARGING UNIT
INSTALLATION
1. Slide the coupling bushing onto the camshaft.

2. Place the gearbox bearing onto the protruding motor

drive shaft, pushing it home until flush with the

mechanism sideplate. If it does not move easily to the

flush position, pull the charging handle gently down to

ease movement.

3. Mount the device using three M5 bolts through the

holes provided in the gearbox endplate, torque to

7 N m.

4. Manually charge the closing springs and carefully locate

the plastic switch actuator over the protruding drive

shaft (Fig. 7.2), ensuring the switch operating arm is

correctly positioned (switch arm should be in the ‘cut

out’ portion of the motor switch actuator.

Figure 7.2. Motor Switch Actuator

5. Use a M8 nylock nut to mount the motor switch

actuator onto the shaft end, torque to 14.5 N m.

6. Connect the motor connector on to the motor harness.

7. Connect the remaining ground wire from the filter to

the grounding point on the rear of the motor body.


Reverse the above procedure to remove the motorized
spring charging unit