TROUBLESHOOTING
Table 8.1 reviews common problems, their possible cause(s) and solution(s). If problems persist please contact our Post Sales
Service Department at 1-888-GERESOLVE (1-888-437-3765).
Table 8.1. Troubleshooting
Problem Possible
Cause
Solution
Breaker won’t close.
Breaker is between CONNECTED, TEST
and DISCONNECTED positions.
Bell alarm has not been reset.
Interlocks installed.
Racking handle inserted.
Rack circuit breaker to CONNECTED, TEST or
DISCONNECTED remove racking handle and close
circuit breaker.
Push BELL ALARM button on trip unit and close
circuit breaker.
Remove interlocks.
Remove handle and close circuit breaker.
Check operational diagram and trip the relevant
circuit breaker.
Breaker closes then opens
instantaneously.
Breaker information module connector
is not inserted.
Insert breaker information module connector to
breaker information module.
Circuit breaker won’t rack into
cassette.
Ensure breaker is pushed fully from the
maintenance position to
DISCONNECTED.
Racking drive not in DISCONNECTED
position.
Push breaker into DISCONNECTED position.
Ensure racking drive is in DISCONNECTED
position.
Cannot insert racking handle.
Shutter padlocks are installed.
Key locks are installed.
Remove padlocks and/or operate key locks.
Circuit breaker will not go into
the DISCONNECTED position.
Circuit breaker is incorrect for given
cassette.
Ensure circuit breaker and cassette go together.
ENTELLIGUARD
®
E PUBLICATIONS
To download publications like those shown below, visit
www.geelectrical.com
.
Publications
Pub #
Entellisys 5.0 Application Guide
DET-838
Entellisys 5.0 User Guide
DEH-501
Bell Alarm w/ Lockout
DEH-41409
Shunt Trip
DEH-41411
Remote Close Accessory Close Coil
DEH-41412
Motor Operator
DEH-41413
Aux Switch
DEH-41415
Network Interlock
DEH-41461*
Remote Racking Operator
DEH-41467
Clusters (Primary Disconnect Fingers)
DEH-41460
Key Interlock (cassette)
DEH-41500
Contact Wear Indicator
DEH-41382
* Secondary disconnect status switch location is different for EntelliGuard E breaker. Status switch position is A33,A34 & A35.