TROUBLESHOOTING

Table 8.1 reviews common problems, their possible cause(s) and solution(s). If problems persist please contact our Post Sales
Service Department at 1-888-GERESOLVE (1-888-437-3765).

Table 8.1. Troubleshooting

Problem Possible

Cause

Solution

Breaker won’t close.

 Breaker is between CONNECTED, TEST

and DISCONNECTED positions.

 Bell alarm has not been reset.
 Interlocks installed.
 Racking handle inserted.

 Rack circuit breaker to CONNECTED, TEST or

DISCONNECTED remove racking handle and close

circuit breaker.

 Push BELL ALARM button on trip unit and close

circuit breaker.

 Remove interlocks.
 Remove handle and close circuit breaker.
 Check operational diagram and trip the relevant

circuit breaker.

Breaker closes then opens
instantaneously.

 Breaker information module connector

is not inserted.

 Insert breaker information module connector to

breaker information module.

Circuit breaker won’t rack into
cassette.

 Ensure breaker is pushed fully from the

maintenance position to
DISCONNECTED.

 Racking drive not in DISCONNECTED

position.

 Push breaker into DISCONNECTED position.
 Ensure racking drive is in DISCONNECTED

position.

Cannot insert racking handle.

 Shutter padlocks are installed.
 Key locks are installed.

Remove padlocks and/or operate key locks.

Circuit breaker will not go into

the DISCONNECTED position.

 Circuit breaker is incorrect for given

cassette.

 Ensure circuit breaker and cassette go together.

ENTELLIGUARD

®

E PUBLICATIONS

To download publications like those shown below, visit

www.geelectrical.com

.

Publications

Pub #

Entellisys 5.0 Application Guide

DET-838

Entellisys 5.0 User Guide

DEH-501

Bell Alarm w/ Lockout

DEH-41409

Shunt Trip

DEH-41411

Remote Close Accessory Close Coil

DEH-41412

Motor Operator

DEH-41413

Aux Switch

DEH-41415

Network Interlock

DEH-41461*

Remote Racking Operator

DEH-41467

Clusters (Primary Disconnect Fingers)

DEH-41460

Key Interlock (cassette)

DEH-41500

Contact Wear Indicator

DEH-41382

* Secondary disconnect status switch location is different for EntelliGuard E breaker. Status switch position is A33,A34 & A35.

Advertising