Installation guide, User interface for setup, Amp1h5 – GE Industrial Solutions AMP1H5 User Manual

Page 11

Advertising
background image

TM

AMP1H5

INSTALLATION GUIDE

ZL0115-0A

PAGE 11

©2013 For technical support please contact

01132

DET-785

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

Next

From:

SETUP > PASWD

Set Current Transducer:

CT V - CT Input Voltage: + or to Select 1.0 or .33V.

CT SZ - CT Size: in Amps. Maximum is 32000 Amps.

Set System Configuration:

SYSTM: + or to step through the following System Type options:

System Reg 130 CTs Description

3L-1n

40

3 Wye Three Phase: A, B, & C with Neutral (Default).

3L

31

3 Delta Three Phase: A, B & C; no Neutral

2L-1n

12

2 Single Split Phase: A & B with Neutral

2L

11

1 Single Phase: A & B; no Neutral

1L-1n

10

1 Single Phase: A to Neutral

System

Type

Current

Transformer

S SYS

Next

S CT

CT V

--------

1.0

.33

CT SZ

--------

200

SYSTM

--------

3L-1n

3L

2L-1n

2L

1L+1n

Bac

k

To

SETU

P

Back

Back

To Setup p. 2 “SPLOS”

Next

S PT

Set Potential Transfomer Ratio:

RATIO – Potential transformer step down is RATIO:1. Default is 1:1

(No PT installed). See Install for wiring diagrams. This value must be

set before the System Voltage (if used).

Potential

Transformer

RATIO

--------

001.00

Back

S V

Back

Sytem

Voltage

Next

Set System Voltage:

V LL – The nominal Line to Line Voltage for the system. This is used

by the meter to calculate the theoretical maximum system power, and

as the reference voltage for setting the Phase Loss threshold.

Maximum is 32000 Volts. For system type 1+N (10), this is a Line to

Neutral Voltage, indicated by “V LN”. Note: the meter will reject settings

that are not within the meter’s operating range when divided by the PT

ratio.

V LL

--------

00480

S PWR

Back

Sytem

Voltage

MX KW

--------

103.92

Next

System Power:

MX KW – The theoretical Maximum System Power is calculated by the

meter from the System Voltage, CT size, and System Type. Power

Factor is assumed to be unity. The value of System Power is used to

determine which combinations of pulse weight and duration are valid

and will keep up with the maximum power the meter will see. This value

is read only.

Note:

Bold is the Default.

Next

MAC

--------

001

KBAUD

--------

115.2

76.8

38.4

19.2

9.6

Set Communications Parameters:

ADDR – BACnet MS/TP MAC Address: 0 – 127.

+ increments the selected (blinking) digit.

selects the digit to the left.

BAUD - Baud Rate: 9600 – 115200 Baud

BACnet ID: These two screens set the 7 digit

BACnet device ID. Screen ID1 is the most

significant 4 digits and ID2 the least significant

three digits. This is in the range of 0 - 4,194,302.

Back

S BAC

To: SPASS

ID1

--------

0000

ID2

--------

000

USER INTERFACE FOR SETUP