Installation guide, Lcd screen: buttons, Quick setup instructions – GE Industrial Solutions AMP1H5 User Manual

Page 7: Display screen diagram, Amp1h5

Advertising
background image

TM

AMP1H5

INSTALLATION GUIDE

ZL0115-0A

PAGE 7

©2013 For technical support please contact

01132

DET-785

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

QUICK SETUP INSTRUCTIONS

Use this section to enter:

- BACnet communication parameters

- CT (Current Transducer) output voltage and input current ranges

- The service type to be monitored

These instructions assume the meter is set to factory defaults. If it has been
previously configured, check all optional values.

A. To Navigate to the Setup screens:

1. Press

+

+

or

repeatedly until SETUP screen appears.

2. Press to get to the PASWD screen.

3. Press to move through the digits. Use the

+

+

or

buttons to enter your

password (the default is 00000).

4. Press to move to the first Setup screen (S BAC)

5. Use

+

+

or

to select the parameter screen you want to set.

6. After you set the parameters you want, use

+

+

or

to select the next Setup

screen or to exit the Setup screens (return to SETUP).

DISPLAY SCREEN DIAGRAM




Tx

Rx

ERR

Screen Name or Units

Diagnostic Alert:

indicates that one or

more of the alarm

bits (Binary_Objects

1-15) are active.

Logo

Numeric Data

Alive Indicator

RS-485 Equipped Units Only:
Transmit Data
Receive Data
Receive Data Error

LCD Screen:

Buttons:

+

(Up)

Select

(Right)

Next

(Down)

Select

(Left)

Back

B. To Enter BACnet communication parameters

1. Navigate to the S BAC (set BACnet) Setup screen (see section A above).

2. Press to go to the MAC screen and through the address digits. Use

+

+

or

to select the BACnet MAC address (default is 001).

3. Press to accept the value and go to the KBAUD screen. Use

+

+

or

to select

the baud rate (default is 76.8K).

4. Press to go to the ID1 screen and through the upper four digits of the Device

Instance. Use

+

+

or

to select the ID digits. The setup screen splits the Device

ID into two parts, the most significant four digits (ID1) and the least significant
three digits (ID2). The AMP1H5 supports BACnet Device ID values from 1 to
4,193,999. Units are shipped with a factory default setting that is pseudo-
randomly generated in the range from 1,000,000 to 3,097,151.

5. Press to accept the value and go to the ID2 screen and through the lower

three digits of the Device Instance. Use

+

+

or

to select the ID digits.

6. Press to accept the value and go back to the S BAC screen.

C. To Enter the CT output voltage and input current ranges:

1. Navigate to the S CT (Set Current Transducer) Setup screen (see section A

above).

2. Press to go to the CT V screen. Use

+

+

or

to select the voltage mode

Current Transducer output voltage (default is 1.00).

3. Press to go to the CT SZ screen and through the digits. Use

+

+

or

to

select the CT size in amps (default is 100). accept the value and

4. Press to accept the value and go back to the S CT screen.

D. To Enter the service type to be monitored:

1. Navigate to the S SYS (Set System) Setup screen (see section A above).

2. Press to go to the SYSTM screen. Use

+

+

or

to select the configuration

(see wiring diagrams - default is 3LN-1N).

Press to go back to the S SYS screen. For full setup instructions, see the
configuration instructions on the following pages.